Tytuł pozycji:
Wyznaczanie parametrów modelu generatora synchronicznego zmodyfikowaną metodą SSFR w oparciu o symulacje MES z uwzględnieniem nasycenia
In this paper the StandStill Frequency Response characteristics (SSFR) of saturated synchronous generator (SG) have been calculated using Finite Element Method (FEM) analysis. It was assumed that the saturation level of the generator core can be taken into account by changing the value of the relative magnetic permeability &mur. In the first step, the simulation is performed in the Magneto Static 2D module and the values of &mur &enspwas determined. In the second step the proper value of the &mur&enspis set in the Steady State AC Magnetic module and the frequency characteristics were determine. In order to validate proposed approach FEM simulation from Flux2D software has been compared with the measurements performed on the 10 kVA, 4-poles synchronous machine ELMOR GCe64a of salient rotor construction, equipped with a damper winding.
W artykule przedstawiono zmodyfikowaną metodę SSFR wyznaczania parametrów modelu generatora synchronicznego z uwzględnieniem nasycenia obwodu magnetycznego. Charakterystyki częstotliwościowe uzyskano na drodze symulacji z wykorzystaniem metody elementów skończonych. Założono, że stan nasycenia rdzenia generatora może zostać uwzględniony poprzez zmianę wartości względnej przenikalności magnetycznej. W pierwszym etapie symulację wykonano w module magneto statycznym, wyznaczono wartość przenikalności względnej. W drugim etapie do obliczeń wykorzystano moduł AC zadając odpowiednią wartość przenikalności magnetycznej rdzenia. W celu weryfikacji zaproponowanej metody wykonano pomiary SSFR i symulacje MES dla generatora synchronicznego o wydatnych biegunach.